← Volver a CVEs
CVE-2023-2071
CRITICAL9.8
Descripcion
Rockwell Automation FactoryTalk View Machine Edition on the PanelView Plus, improperly verifies user’s input, which allows unauthenticated attacker to achieve remote code executed via crafted malicious packets. The device has the functionality, through a CIP class, to execute exported functions from libraries. There is a routine that restricts it to execute specific functions from two dynamic link library files. By using a CIP class, an attacker can upload a self-made library to the device which allows the attacker to bypass the security check and execute any code written in the function.
Detalles CVE
Puntuacion CVSS v3.19.8
SeveridadCRITICAL
Vector CVSSCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Vector de ataqueNETWORK
ComplejidadLOW
Privilegios requeridosNONE
Interaccion usuarioNONE
Publicado9/12/2023
Ultima modificacion11/21/2024
Fuentenvd
Avistamientos honeypot0
Productos afectados
rockwellautomation:factorytalk_viewrockwellautomation:panelview_plus
Debilidades (CWE)
CWE-20CWE-434
Referencias
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724(PSIRT@rockwellautomation.com)
https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1140724(af854a3a-2127-422b-91ae-364da2661108)
Correlaciones IOC
Sin correlaciones registradas
This product uses data from the NVD API but is not endorsed or certified by the NVD.